Recently Viewed Items

Clear this list

Newsletter

3M™ Fire Barrier CP 25WB+ Caulk


Description of 3M™ Fire Barrier CP 25WB+ Caulk

Scroll to Pricing

3M Fire Barrier CP 25WB+ Caulk formula is water based and halogen free, this makes for easy clean up and safe handling when applying the product. Perfect for overhead and vertical applications, the latex sealant quickly bonds and dries to concrete, metal, wood, and plastic.

Protecting from flame, noxious gas, smoke and water, the CP 25WB+ Fire Barrier Caulk will expand up to 3 times at 1000F to seal around parts restoring fire rated construction to original integrity.

-UL Listed
-FM Approved

Please click the "More Information" tab for detailed specs on this product.

*5 Day Lead Time on 5 gallon Pail


Review this item After receiving your order add a new product review here and receive 10% Off on your next order!!

Features and Benefits

  • [product_feature_name]

More Info

Typically Specified Divisions
Division 7
07270
Thermal and Moisture Protection Firestopping
Division 13
13900
Special Construction Fire Suppression and Supervisory System
Division 15
15250
15300
MechanicalMechanical Insulation Fire Protection
Division 16 Electrical
1650
ElectricalBasic Electrical Materials and Methods

Performance
  Unit Value
Tack Free Time
(ASTM C679-87)
Minutes at 72F (22C) 10-15
Expansion at 662F (350C) x 2.0-3.0
Color - Reddish Brown
Density Lb./gal. (Kg/l) 11.2 (1,35)
Adhesion All construction substrates Very Good
Application Method Caulk guns, trowel, spatula, pressurized pumps
Durometer (hardness) Shore A 70
ASTM E 84
  Flame Spread
  Smoke Development

-
-

5
0
Solids Percent (%) by weight 79
VOC Percent (%) by weight 0
Odor - Pleasant, non-irritating
Flow Rate
  1/4 in. (6.35mm)
  nozzle at 50 psi
Grams/min. 1000
Boeing Flow
(Sag Characteristice)
Inches 0

Firestopping Properties
Meets the criteria of ASTM E 814 Fire Test, tested under positive pressure.
Consult current UL Fire Resistance Directory for systems listed under 3M Product CP 25WB+ Caulk.

ICBO Uniform Building Code (1997 Edition)
SBCCI Standard Building Code (1997 Edition)
BOCA Basic/National Building Code (1996 Edition)
NFPA Life Safety Code 101 (1997 Edition)
702 DEFINITIONS

706 CONSTRUCTION JOINTS

708 WOOD FRAME CONSTRUCTIONFIREBLOCKING

709WALL & PARTITION PENETRATIONPORTECTION

709.3.2.2 CURTAIN WALL GAP

710 FLOOR/CEILING OR ROOF/CEILING PENETRATION PROTECTION

711.3 SHAFT ALTERNATIVE

714 THROUGH-PENETRATION FIRE STOPS F&T REQUIREMENTS

UBC STANDARD 7-1 EQUIVALENT TO ASTM E 119

UBC STANDARD 7-5 EQUIVALENT TO ASTM E 814
104.2.4PLANS MUST SHOW HOW INTEGRITY IS MAINTAINEDFOR ASSEMBLIES PENETRATED

202DEFINITIONS

705.3 WOOD FRAME CONSTRUCTION FIRE BLOCKING

705.3.1.5 CURTAIN WALL GAP

705.4 (GENERAL)PENETRATIONS OF FIRE RATED ASSEMBLIES

705.5 (WALLS)

705.6 (FLOORS)

705.7 FIRE RESISTANT JOINT SYSTEMS
702.0
REVISED AND EXPANDED
DEFINITIONS
FOR PENETRATIONS AND
JOINTS

703.1
CONSTRUCTION
DOCUMENTS SHALL
INDICATE DETAILS AND
MATERIAL FOR PROVIDING
RATINGS AT JOINTS AND
PENETRATIONS

703.1.1
PENETRATIONS AND JOINTS
SHALL NOT BE CONCEALED
FROM VIEW BEFORE
INSPECTION

703.2
BUILDINGS FOR MORE THAN
TWO STORIES SHALL
INDICATE ALL
PENETRATIONS

704.1.1
SUFFICIENT DATA SHALL BE
AVAILABLE TO JUSTIFY
UNTESTED MATERIALS
USED FOR RESTORATION
OF FIRE RATINGS

707.10
PENETRATIONS-REFERS
TO 714

707.8
JOINTS-REFERS TO

709.7

709.0
FIRE SEPARATION
ASSEMBLIES
709.6
PENETRATIONS-REFER
TO 714

709.7
JOINTS

711.0
FIRE PARTITIONS

711.6
PENETRATIONS -
REFERS TO 714

711.7
JOINTS-REFER TO 709.7

713.0
FLOOR/CEILING AND
ROOF/CEILING
ASSEMBLIES

713.2
CURTAIN WALL GAP

713.4
PENETRATIONS-
REFERS TO 714

713.5
JOINTS-REFERS TO
709.7

714.0
PENETRATIONS-ALL
REQUIREMENTS
(GENERAL)

714.1 THROUGH 714.1.6.2
WALL ASSEMBLIES

714.2 THROUGH 714.2.6.5
FLOOR/CEILING AND
ROOF/CEILING
ASSEMBLIES

714.3 THROUGH 714.3.2
NONRATED ASSEMBLIES

721.0
FIREBLOCKING AND
DRAFTSTOPPING
6-2.3.2.4
PENETRATIONS AND
MISC. OPENINGS&FIRE
BARRIERS

6.2.4.2, EXCEPTION
5 OPENINGS (EXPANSION
OR SEISMIC JOINTS) IN
FLOORS

APPENDIX
A-6-2.4.2

6-3.6.1
PENETRATIONS AND
MISC. OPENINGS
IN FLOORS AND SMOKE
BARRIERS

NFPA #221

FIRE WALLS
NFPA
Code 70 NEC
National Electric Code


300-21 FIRESTOPPING
CABO
One and Two family
Dwelling Code
(1995 Edition)


602.7
FIRESTOPPING
(FIREBLOCKING IN OTHER
MODEL CODES)