Series 22 |
Series 33 |
Series 44 |
| Application |
Walls only |
Walls & Floors |
Walls & Floors |
| Height x Width |
1.5" x 1.5"(38mm x 38mm) |
3.0" x 3.0"(76mm x 76mm) |
4" x 4-5/8"(102mm x 118mm) |
| Length |
10.5" (267mm) |
10.5 (267mm) |
14" (356mm) |
| Volume Expansion |
15X |
16X |
16X |
| Can be Ganged |
no |
up to 7 |
up to 5 in wall of 16 in floor |
| Can be Lengthened |
no |
6" (152mm) increments |
no |
| Insert into Cored Hole |
2" (51mm) |
4" (102mm) |
6" (153mm) |
| Attached to Conduit |
no |
4" (102mm) |
no |
| Fire Rated in Walls |
up to 2 hours |
up tp 4 hours |
up to 4 hours |
| Fire Rated in Floors |
n/a |
up to 4 hours |
up to 4 hours |
| Approx Max Cable Capacity |
25± |
120± |
244± |
| Approx Max Cable Capacity (Ganged) |
n/a |
840± |
1220± |
| Approx Max Cable Capacity (Grid) |
n/a |
n/a |
3904 ± in floors |
| Shell Composition |
0.059" (1.5mm) Galvanized Steel |
0.059" (1.5mm) Galvanized Steel |
0.059" (1.5mm) Galvanized Steel |
| Cable Loading Area |
1.25 square in (nom) (8.06 cm²) |
6 square in (nom) (38.71 cm²) |
6 square in (nom) (38.71 cm²) |
| Allowable Fill |
100% visual |
100% visual |
100% visual |
| Expansion Begins |
350°F (177°C) |
350°F (177°C) |
350°F (177°C) |
| CAT5/CAT6 |
25 (nom)/18 (nom) |
120 (nom)/90 (nom) |
244 (nom)/175 (nom) |
| In Service Temperature |
≤ 120°F (49°C) |
≤ 120°F (49°C) |
≤ 120°F (49°C) |
| Shelf Life |
No limit |
No limit |
No limit |
| UL Ratings |
UL 1479 |
UL 1479 |
UL 1479 |
| ASTM Ratings |
ASTM E814 Div 7 07840 - Through-Penetration Firestopping ASTM E814 Div 18 16050 - Basic Electrical Materials and Methods |
ASTM E814 Div 7 07840 - Through-Penetration Firestopping ASTM E814 Div 18 16050 - Basic Electrical Materials and Methods |
ASTM E814 Div 7 07840 - Through-Penetration Firestopping ASTM E814 Div 18 16050 - Basic Electrical Materials and Methods |