Recently Viewed Items

Clear this list

Newsletter

STI Firestop E-Z Path® Fire Rated Cableway


FR-STI-EZDP133CWK: Series 33 Fire-Rated Circular Wall Plate Pack (full kit with 2 circular wall plates) installed in wall.

Description of STI Firestop E-Z Path® Fire Rated Cableway

Scroll to Pricing

Specified Technologies E-Z Path Firestop Fire Rated Cableway offers exceptional protection against fire and smoke while making installation simple and clean. Run cables through fire rated walls and floors using the EZ-Path fire protection system with no additional materials and still holding the fire rated status.

A creative spring loaded base combined with arched intumescent foam pads conform to different size cable bundles allowing for easy maintenance and when heated the intumescent pads will expand creating a seal in the E-Z Pathway preventing fire pass-through.

UL Classified and FM approved in accordance with ASTM E-814 (UL 1479)

U.S. Patent 6,732,481

Click the "More Informaiton" tab for Fill Capacity Chart and additional data.


Review this item After receiving your order add a new product review here and receive 10% Off on your next order!!

Features and Benefits

  • [product_feature_name]

More Info

Shell Composition 0.059" galvanized steel
Cable Loading Area 6 sq in (nom)
Allowable Cable Fill 100% visual
Fire Resistance Rating 1 and 2 hour
Expansion Begins 350F (176C)
Volume Expansion 800%
Sample Cable Volume (CAT5) 120 (nom)
In-Service Temperature ≤ 120F (49C)

Fill Capacity Chart

Cable Diameter
Pathway Cable Capacity
mm
inches
EZD22
EZD33
EZD44
3
0.118
78
395
822
3.5
0.138
57
290
604
4
0.157
44
222
462
4.5
0.177
34
175
365
5
0.197
28
142
296
5.5
0.216
23
117
244
6
0.236
19
98
205
6.5
0.256
16
84
175
7
0.275
14
72
151
8
0.314
11
55
115
9
0.354
8
43
91
12.5
0.491
4
22
47
15
0.590
3
15
32
18
0.708
2
10
22
20
0.786
1
8
18
25
0.983
1
5
11
30
1.179
0
3
8
35
1.376
0
2
6

 

Product Selection Guide

  Series 22 Series 33 Series 44
Application Walls only Walls & Floors Walls & Floors
Height x Width 1.5" x 1.5"(38mm x 38mm) 3.0" x 3.0"(76mm x 76mm) 4" x 4-5/8"(102mm x 118mm)
Length 10.5" (267mm) 10.5 (267mm) 14" (356mm)
Volume Expansion 15X 16X 16X
Can be Ganged no up to 7 up to 5 in wall of 16 in floor
Can be Lengthened no 6" (152mm) increments no
Insert into Cored Hole 2" (51mm) 4" (102mm) 6" (153mm)
Attached to Conduit no 4" (102mm) no
Fire Rated in Walls up to 2 hours up tp 4 hours up to 4 hours
Fire Rated in Floors n/a up to 4 hours up to 4 hours
Approx Max Cable Capacity 25 120 244
Approx Max Cable Capacity (Ganged) n/a 840 1220
Approx Max Cable Capacity (Grid) n/a n/a 3904 in floors
Shell Composition 0.059" (1.5mm) Galvanized Steel 0.059" (1.5mm) Galvanized Steel 0.059" (1.5mm) Galvanized Steel
Cable Loading Area 1.25 square in (nom) (8.06 cm) 6 square in (nom) (38.71 cm) 6 square in (nom) (38.71 cm)
Allowable Fill 100% visual 100% visual 100% visual
Expansion Begins 350F (177C) 350F (177C) 350F (177C)
CAT5/CAT6 25 (nom)/18 (nom) 120 (nom)/90 (nom) 244 (nom)/175 (nom)
In Service Temperature ≤ 120F (49C) ≤ 120F (49C) ≤ 120F (49C)
Shelf Life No limit No limit No limit
UL Ratings UL 1479 UL 1479 UL 1479
ASTM Ratings ASTM E814 Div 7 07840 - Through-Penetration Firestopping ASTM E814 Div 18 16050 - Basic Electrical Materials and Methods ASTM E814 Div 7 07840 - Through-Penetration Firestopping ASTM E814 Div 18 16050 - Basic Electrical Materials and Methods ASTM E814 Div 7 07840 - Through-Penetration Firestopping ASTM E814 Div 18 16050 - Basic Electrical Materials and Methods